dc.contributor.author | Martínez Torre, Raquel | |
dc.contributor.author | Mañana Canteli, Mario | |
dc.contributor.author | Rodríguez Alonso, José Iván | |
dc.contributor.author | Álvarez, Marcos | |
dc.contributor.author | Arroyo Gutiérrez, Alberto | |
dc.contributor.author | Bayona Blanco, Eduardo | |
dc.contributor.author | Azcondo Sánchez, Francisco Javier | |
dc.contributor.author | Pigazo López, Alberto | |
dc.contributor.author | Francisco, Cuartas | |
dc.contributor.other | Universidad de Cantabria | es_ES |
dc.date.accessioned | 2025-01-29T12:44:45Z | |
dc.date.available | 2025-01-29T12:44:45Z | |
dc.date.issued | 2019-01 | |
dc.identifier.issn | 1752-1416 | |
dc.identifier.uri | https://hdl.handle.net/10902/35231 | |
dc.description.abstract | Power quality events associated with the occurrence of ferroresonances in medium voltage (MV) isolated-neutral distribution power systems are well known but they still happen in nowadays grids. This work deals with the study of ferroresonance events in a distribution grid region characterised by having distributed generators and being lightly loaded. The study shows that well-known solutions, i.e. voltage transformer damping, are difficult to apply due to the legal considerations and, alternatively, the distribution system operator can take actions to minimise their effect on the distribution system. The data provided and the obtained results correspond to a three-year measurement campaign at a real MV isolated-neutral distribution power system. The measurements and analysis given allow reaching general conclusions about the distribution system operation oriented to minimise the effect of ferroresonances. | es_ES |
dc.description.sponsorship | This work was supported by the Spanish government and FEDER funds of the European Union under RETOS RTC-2015-4176-3, Innovation in the automation of the isolated neutral distribution.The authors also acknowledge the support received from Viesgo S.L across all the activities in the project above. The authors would also like to thank Arteche for the collaboration in the characterisation of some of the VTs. | es_ES |
dc.format.extent | 6 | es_ES |
dc.language.iso | eng | es_ES |
dc.publisher | The Institution of Engineering and Technology | es_ES |
dc.rights | Alojado según Resolución CNEAI 9/12/24 (ANECA) © The Institution of Engineering and Technology 2018 | es_ES |
dc.source | IET Renewable Power Generation, 2019, 13(1), 209-214 | es_ES |
dc.title | Ferroresonance phenomena in medium-voltage isolated neutral grids: a case study | es_ES |
dc.type | info:eu-repo/semantics/article | es_ES |
dc.relation.publisherVersion | https://doi.org/10.1049/iet-rpg.2018.5231 | es_ES |
dc.rights.accessRights | closedAccess | es_ES |
dc.identifier.DOI | 10.1049/iet-rpg.2018.5231 | |
dc.type.version | publishedVersion | es_ES |