Detection of ferroresonance occurrence in inductive voltage transformers through vibration analysis
Ver/ Abrir
Registro completo
Mostrar el registro completo DCAutoría
Arroyo Gutiérrez, Alberto




Fecha
2019-03Derechos
© 2018. This manuscript version is made available under the CC-BY-NC-ND 4.0 license
Publicado en
International Journal of Electrical Power and Energy Systems, 2019, 106, 294-300
Editorial
Elsevier
Enlace a la publicación
Palabras clave
Ferroresonance
Inductive voltage transformer
Power transformer
Resumen/Abstract
Steady state ferroresonances in isolated neutral electrical systems result in sustained abnormal system oscillations, which can damage inductive voltage transformers (IVTs) and other system elements. During this phenomenon, the IVT becomes saturated; consequently, the dimensions of the ferromagnetic material of the IVT change owing to magnetostriction. Because of this inherently nonlinear behaviour, the natural vibration modes of the IVT are excited. The aim of this study is to take advantage of these anomalous vibration modes to reveal the occurrence of ferroresonance in IVTs. The methodology for ferroresonance detection in IVTs through vibration analysis is described and demonstrated experimentally.