Distinction between arcing faults and oil contamination from OLTC gases
Ver/ Abrir
Registro completo
Mostrar el registro completo DCAutoría
Bustamante Sánchez, Sergio


Fecha
2024Derechos
© 2024 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution ( CC BY) license.
Publicado en
Electronics, 2024, 13(7), 1338
Editorial
MDPI
Palabras clave
Communicating OLTC
Dissolved gas analysis
Fault-identification method
Oil insulation
Power transformer
Resumen/Abstract
Power transformers are the most important and expensive assets in high-voltage power systems. To ensure an adequate level of reliability throughout the transformer’s lifetime, its maintenance strategy must be well defined. When an incipient fault occurs in the transformer insulation, a gas concentration pattern, representative of the type of fault, is generated. Fault-identification methods use gas concentrations and their ratios to identify the type of fault. None of the traditional or new fault-identification methods attempt to detect transformer oil contamination from on-load tap changer (OLTC) gases. In this study, from dissolved gas analysis (DGA) samples of transformers identified as contaminated in a previous study, fault-identification methods based on graphical representations were used to observe the patterns of results. From such patterns, Duval’s triangle and pentagon methods were modified to include a new zone indicating oil contamination (OC) from OLTC gases. Finally, the proposed modifications were validated using 75 DGA samples extracted from previous studies that were identified as D1 or D2 faults or contaminated from OLTC. This validation showed that only 14.7% and 13.3% of the DGA samples fell within the new OC zone of the proposed triangle and pentagon, respectively.
Colecciones a las que pertenece
- D19 Artículos [94]
- D19 Proyectos de investigación [102]