dc.description.abstractThe deterioration of the insulation in the windings of power transformers affects their lifespan. A commercial insulated Continuously Transposed Conductor (CTC) was studied experimentally, numerically and analytically. The purpose was to understand the mechanisms governing the mechanical failure of the insulating paper, and to achieve a criterion for predicting failure under different conditions. Samples of that insulated CTC were extracted from a coil and aged at 150∘C for different durations inside vessels filled with naphthenic oil. Then the degree of polymerisation and tensile, compressive and shear mechanical properties of the insulation were measured/estimated. Aged insulated CTC samples were subjected to three-point bending tests, producing deformations compatible with a short circuit, and the fractures in the insulation were analysed. The bending test over a CTC sample was simulated by means of a FEM Program. The Norris failure model, applicable to a lamina, was adapted to the studied insulation materials. The predictions of that failure criterion agreed with experimental observations.es_ES
dc.format.extent5 p.es_ES
dc.language.isoenges_ES
dc.publisherInstitute of Electrical and Electronics Engineers, Inc.es_ES
dc.rights© 2022 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.es_ES
dc.sourceIEEE 4th International Conference on Dielectrics (ICD): procceedings, Palermo, Italy, 2022, 813-816es_ES
dc.titleA modification of the Norris failure criterion for the prediction of the mechanical failure of the aged paper insulation in the windings of a power transformeres_ES
dc.typeinfo:eu-repo/semantics/conferenceObjectes_ES
dc.relation.publisherVersionhttps://doi.org/10.1109/ICD53806.2022.9863458es_ES
dc.rights.accessRightsopenAccesses_ES
dc.identifier.DOI0.1109/ICD53806.2022.9863458
dc.type.versionacceptedVersiones_ES


Ficheros en el ítem

Thumbnail

Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo