Mostrar el registro sencillo

dc.contributor.authorLamo Anuarbe, Paula
dc.contributor.authorPigazo López, Alberto 
dc.contributor.authorAzcondo Sánchez, Francisco Javier 
dc.contributor.otherUniversidad de Cantabriaes_ES
dc.date.accessioned2021-08-03T15:54:20Z
dc.date.available2021-08-03T15:54:20Z
dc.date.issued2021-06
dc.identifier.issn2168-6777
dc.identifier.issn2168-6785
dc.identifier.otherRTI2018-095138-B-C31es_ES
dc.identifier.urihttp://hdl.handle.net/10902/22090
dc.description.abstractThe two-sample phase locked loop (2S PLL) in single-phase digitally controlled grid-connected power converters provide synchronization with a minimal computational burden. However, the distortion of the grid voltage deteriorates the performance of the 2S quadrature signal generator. To solve this issue, this article introduces a harmonic filtering (HF) structure based on observers of the input voltage for the fundamental and selected harmonics. The stability and sensitivity of the 2S PLL with HF is analyzed. In comparison with second-order generalized integrator (SOGI)-based HF, the observers provide a narrower bandpass, and the subsequent deterioration of the response time is compensated by adapting the filter gains dynamically. The results obtained, both in simulation and experimentally, validate the proposal and compare its performance with other widely adopted PLLs providing harmonic rejection capability. The computational burden is analyzed and in the case of the proposals depends on the number of observers and the use or not of the adaptive strategy based on steepest descent.es_ES
dc.description.sponsorshipThis work has been supported by the Spanish Ministry of Science and Innovation under Project RTI2018-095138-B-C31 PEGIA Power Electronics for the Grid and Industry Applications.es_ES
dc.format.extent11 p.es_ES
dc.language.isoenges_ES
dc.publisherInstitute of Electrical and Electronics Engineerses_ES
dc.rights© 2021 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.es_ES
dc.sourceIEEE Journal of Emerging and Selected Topics in Power Electronics, 2021, 9(3), 3072-3082es_ES
dc.subject.otherAC–DC power converterses_ES
dc.subject.otherAdaptive filterses_ES
dc.subject.otherHarmonic distortiones_ES
dc.subject.otherPhase locked loops (PLLs)es_ES
dc.subject.otherRectifierses_ES
dc.titleTwo-sample PLL with harmonic filtering capability applicable to single-phase grid-connected converterses_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.relation.publisherVersionhttps://doi.org/10.1109/JESTPE.2020.2997847es_ES
dc.rights.accessRightsopenAccesses_ES
dc.identifier.DOI10.1109/JESTPE.2020.2997847