dc.description.abstractIn the present article the voltage drop in a low voltage isolated cable is analyzed by the authors. This analysis considers the effect of resistivity variation with the temperature; which, as well, depends on the current. It makes to them to define the ‘temperature factor’. The authors demonstrate that the voltage drop due to the cable reactance cannot be neglected when temperature effects are taken into account. Finally, it is shown two fast, simple and systematic methods to calculate the cross-section of a LV isolated cable. These methods consider the cable real temperature and reactance. One of them is analytical and the other uses the tables of per unit voltage drop provided by manufacturers and standards.es_ES
dc.format.extent6 p.es_ES
dc.language.isoenges_ES
dc.publisherWorld Scientific and Engineering Academy and Society (WSEAS)es_ES
dc.rights© World Scientific and Engineering Academy and Society (WSEAS)es_ES
dc.sourceWSEAS Transactions on Circuits and Systems, 2005, 4(9), 1112-1117es_ES
dc.subject.otherIsolated cableses_ES
dc.subject.otherVoltage dropes_ES
dc.subject.otherTemperaturees_ES
dc.subject.otherLow voltagees_ES
dc.subject.otherResistivityes_ES
dc.titleTemperature factor for the accurate calculation of LV cableses_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.rights.accessRightsopenAccesses_ES
dc.type.versionpublishedVersiones_ES