Mostrar el registro sencillo

dc.contributor.authorMañana Canteli, Mario 
dc.contributor.authorEguíluz Morán, Luis Ignacio
dc.contributor.authorLavandero González, José Carlos 
dc.contributor.authorDíez Cagigal, Gerardo 
dc.contributor.otherUniversidad de Cantabriaes_ES
dc.date.accessioned2020-11-06T17:01:17Z
dc.date.available2020-11-06T17:01:17Z
dc.date.issued2003-04
dc.identifier.isbn84-607-6768-X
dc.identifier.issn2172-038X
dc.identifier.urihttp://hdl.handle.net/10902/19594
dc.description.abstractPower Quality measurements involve not only problems related with the real use of recorders but also theoretical questions connected with functional and design aspects of the instrumentation. In addition, there are a rising number of standards covering topics from design to data analysis, so final users usually assume that they do not have to pay special attention to PQ instrumentation functionality when the device is designed according to approved standards. However, it is not unusual to find different disturbances at the same point and in the same time and standards do not say anything about their mutual influence on PQ index. The main aim of this research work is to show the influence that having different disturbances (flicker and sags) simultaneously has on the final results provided by the instrumentation for each individual disturbance. The paper proposes a test system and a methodology. The results of various tests using commercial and research instrumentation are presented and some possible solutions to these problems are considered.es_ES
dc.format.extent5 p.es_ES
dc.language.isoenges_ES
dc.publisherEuropean Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ)es_ES
dc.rights© The European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ)es_ES
dc.sourceRenewable Energy and Power Quality Journal (RE&PQJ), 2003, 1(1), 324-328es_ES
dc.sourceInternational Conference on Renewable Energies and Power Quality (ICREPQ’03), Vigoes_ES
dc.subject.otherPower Qualityes_ES
dc.subject.otherFlickermeteres_ES
dc.subject.otherFlickeres_ES
dc.subject.otherHarmonicses_ES
dc.subject.otherSages_ES
dc.subject.otherDisturbanceses_ES
dc.titleInfluence on power quality measurement of the simultaneous presence of different disturbanceses_ES
dc.typeinfo:eu-repo/semantics/conferenceObjectes_ES
dc.rights.accessRightsopenAccesses_ES
dc.identifier.DOI10.24084/repqj01.376
dc.type.versionpublishedVersiones_ES


Ficheros en el ítem

Thumbnail

Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo