dc.description.abstractIn this paper, an experimental and numerical research was conducted to study the aging effect on the cooling performance of a natural ester habitually used in power transformers. A monitored experimental platform has been used to observe the temperature increases with the aging of the ester. Three samples with three aging levels (fresh oil, aged oil and aged oil with paper) were tested at three load levels, C = 0.72, C = 1 and C = 1.3 (9 tests). The two aged samples (6 liters each) were aged in an accelerated way within an oven: 1 week at 150 °C. Also, some physicochemical properties of the insulation system were determined. In the case of the liquid, viscosity, moisture, acidity, dissipation factor (90 °C) were measured. The degree of polymerization and the moisture were measured in paper samples. A 2D numerical model has been developed with COMSOL Multiphysics to replicate the thermal-hydraulic behavior of the samples in the platform. That is, the idea is to determine the temperature and velocity distributions of the different samples in order to analyze their differences and to compare their cooling capacity. At first sight, the aging affects negatively to the cooling capacity of the new alternative liquid based on natural esters.es_ES
dc.description.sponsorshipThe research leading to these results has received funding from multiple sources over years, but we would specifically like to acknowledge the support received in the later stages from the Spanish Plan Estatal de I+D under the grant agreement DPI2015-71219-C2-1-R.es_ES
dc.format.extent11 p.es_ES
dc.language.isoenges_ES
dc.publisherElsevier Ltdes_ES
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 International*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/*
dc.sourceApplied Thermal Engineering, 2018, 144, 797-803es_ES
dc.subject.otherNatural esteres_ES
dc.subject.otherThermal aginges_ES
dc.subject.otherPSP paperes_ES
dc.subject.otherExperimental platformes_ES
dc.subject.other2D numerical modeles_ES
dc.subject.otherCooling capacityes_ES
dc.titleThe aging impact on the cooling capacity of a natural ester used in power transformerses_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.relation.publisherVersionhttps://doi.org/10.1016/j.applthermaleng.2018.08.049es_ES
dc.rights.accessRightsopenAccesses_ES
dc.identifier.DOI10.1016/j.applthermaleng.2018.08.049