Quantification of Kraft paper ageing in mineral oil impregnated insulation systems through mechanical characterization
Ver/ Abrir
Registro completo
Mostrar el registro completo DCAutoría
Carrascal Vaquero, Isidro Alfonso





Fecha
2018-06Derechos
© Springer. This is a post-peer-review, pre-copyedit version of an article published in Cellulose. The final authenticated version is available online at: https://doi.org/10.1007/s10570-018-1788-1
Publicado en
Cellulose, 2018, 25(6), 3583-3594
Editorial
Springer Nature
Enlace a la publicación
Palabras clave
Kraft paper
Power transformer
Thermal ageing
Degradation
Tensile test
Degree of polymerisation
Resumen/Abstract
Power transformers use Kraft paper, thermally upgraded Kraft and other polymeric papers (ex. Nomex) as the main solid insulation between the winding conductors. Dielectric oil used in transformers as an insulating and cooling fluid typically has an operating temperature range of 60–90 °C. These service temperatures can cause slow degradation of both the oil and the insulating paper winding, with a loss of mechanical and dielectric properties. In this sense, this work analyzes paper degradation through Young’s Modulus, yield stress, rupture strength and strain under ultimate strength. An accelerated thermal ageing of the paper in mineral oil was carried out at temperatures of 110, 130 and 150 °C over different periods of time, in order to obtain information on the kinetics of the ageing degradation of the paper. The evolution of the mechanical properties and micro mechanisms of paper failure are analysed as a function of temperature and ageing time. Finally, the results obtained are compared with the traditional method of degradation analysis, based on the degree of polymerisation measurement.
Colecciones a las que pertenece
- D03 Artículos [296]
- D03 Proyectos de Investigación [178]
- D19 Artículos [94]
- D19 Proyectos de investigación [102]